What are the modes of operation of the voltage regulator?
OFF - manual (DC adjuster)
TEST - manual (DC adjuster). AC adjuster gets power, but is not controlling
ON - auto (AC adjuster)
How does the voltage regulator operate in auto mode (AC adjuster)?
Senses generator voltage (terminal voltage) and maintains it at setpoint
How does the voltage regulator operate in manual mode (DC adjuster)?
How does the voltage regulator, exciter, and generator work to produce voltage to be sent to the grid?
What is the purpose of the permanent magnet generator?
Provides power to the voltage regulator for field excitation
What is the purpose of the exciter?
Provides current to the rotor field
What is the purpose of the rectifier wheels?
Turns AC current from the exciter to DC current to be supplied to the main generator field windings on the rotor.
What is the required response to blown fuses on the rectifiers?
What is the purpose of the field breaker?
Connects the PMG to the voltage regulator
What happens if the field breaker is opened while at power?
Loss of excitation alarm and 386P relay actuates, which will trip the plant
What is the process for transferring the voltage regulator from manual to auto?
What is the function of the 386P/B relays?
Trips the turbine/generator on electrical faults that would make you not want to use the coast down feature.
What happens when the 386P/B relays actuate?
What is the function of the 386C relay?
Trips the turbine/generator on non-electrical faults that you would want to use the coast down feature.
What happens when the 386C relay actuates?
What is the function of the minimum excitation limiter?
- 21.7 KV minimum excitation
What is the function of the loss of field relay?
What is the function of the volts/Hz limiter?
What is the function of the maximum excitation limiter?
- Only works with AC adjuster
What is the function of the regulator over excitation module?
What is the purpose of the stator coil hot gas temperature PPC alarm?
- indicates a hot spot in the stator, and there may be generator damage
What is the consequence of high cold gas temperature?
Reduces the life of gaskets and seals, and eventual H2 leak