LCO 3.4.9 “Pressurizer” requirements
The pressurizer shall be operable with:
LCO 3.4.9 “Pressurizer” applicability
Modes 1-3
What is the purpose of the PZR level control system?
Maintains PCS pressure and compensates for changes in volume during load changes.
What is the relationship between power level, Tave, and PZR level?
0% power = 532 F Tave = 42% PZR level
100% power = 560 F Tave = 57% PZR level
How does the PZR level control system control PZR level?
What are the power supplies for the PZR level controllers?
LIC-0101A from Y-10
LIC-0101B from Y-20
How does the PZR level control system respond to a lowering PZR level?
Sends a signal for more charging (raising P-55A speed or starting P-55B and/or P-55C) and less letdown (closing letdown orifice stop valves)
How does the PZR level control system respond to a rising PZR level?
Sends a signal for less charging (lowering P-55A speed or stopping P-55B and/or P-55C) and more letdown (opening letdown orifice stop valves)
What are the modes of operation of the PZR level controllers?
CASCADE - receives a signal from selected Tave controller and generates a PZR level setpoint
AUTO - operator selects a PZR level setpoint for the controller to maintain
MANUAL - operator controls output signal with slide bar on the controller
How does the PZR backup level control work?
How is the out of service PZR level controller maintained and why?
Maintained in MANUAL with output set to 50%. This is to keep the controller immediately available for use, and to prevent it from becoming “saturated” due to “fighting” the in service controller if setpoints are slightly different.
What is indicated on the PZR level recorders?
How many gallons/% in the PZR?
66
How many gallons/% in the VCT?
34
What is the PZR Hi/Lo level alarm setpoint?
5.75% deviation from setpoint
What is the PZR Lo-Lo level alarm setpoint?
36%
What is the PZR High level alarm setpoint?
49% cold calibrated level (equivalent to approximately 75% hot calibrated level)
What is the order of equipment operation as PZR level lowers, if PZR level is initially high with all letdown orifice stop valves open, and only the ‘A’ Charging Pump is running?
What is the order of equipment operation as PZR level rises, if PZR level is initially low with all letdown orifice stop valves closed, and all 3 charging pumps running?
How can the PZR level control system be operated manually without the backup PZR level control overriding?
How is PZR level control affected by a loss of Y-10?
How is PZR level control affected by a loss of Y-20?
How is PZR level control affected by a loss of Y-01?
PZR level controllers have power, but the switches that receive signals from the normal and backup level control programs don’t have power. This causes MAX charging and ZERO letdown.