What components are powered from Bus 141?
1A CV PP, 0A VC chiller, 1A AF pp, 1A CS pp, 1A RH pp, 1A SI pp, 1A SX pp, 1A CC pp, 0 CC pp, 0A AB supply, 0A AB exhaust, Bus 131X, Bus 131Z
What components are powered from bus 142?
0CC pp, Bus 132X, Bus 132Z, 1B CC pp, 1B CS pp, 1B RH pp, 1B SI pp, 1B SX pp, 1B CV pp, 0B AB Exhaust, 0B AB supply, 0B VC chiller
What components are powered from bus 143?
Bus 033W, Bus 133U, Bus 133V, Bus 133X, Bus 133Y, Bus 133Z, warehouse/gatehouse, 1A CW pp, 1C CW pp, 0A WS pp, 1A VP chlr, 1A SAC, PZR heaters GRP-A and GRP-D
What components are powered from bus 144?
PZR heaters B/U grp-B, PZR heaters Var grp-C, Bus 134U, Bus 134V, Bus 134X, Bus 134Y, Bus 134Z, 0B WS pp, 1B VP chlr, 1B CW pp, 0A fire pp, 1B SAC, Bus 034R, Bus 034P, Bus 034W, 0A SB chlr, 0A VA chlr
What components are powered from bus 156?
1B RCP, 1B HD pp, 1A FW pp
What components are powered from bus 157?
RSH transformers, 1A HD pp, 1C HD pp, 1A RCP
What components are powered from bus 158?
1C RCP, 1D CD/CB pp, 1B CD/CB pp
What components are powered from bus 159?
1D RCP, 1A CD/CB pp, 1C CD/CB pp, SU fw pp
What are the normal power supplies for busses 141, 142, 143, 144, 156, 157, 158, 159?
SAT- 141, 142, 158, 159
UAT- 143, 144, 156, 157
What interlocks exist to supply power from the ESF to non ESF? 1411 breaker interlocks
What are the interlocks to close the SAT feed breaker to bus 141? Breaker 1412
What interlocks must be satisfied to manually close DG output breaker? Breaker 1413
D/G up to speed and voltage
Syncscope on
Bus energized (Hacker relay energized)
What interlocks must be satisfied to auto close DG output breaker? - example Breaker 1413
D/G speed and voltage ESF to non esf open 1411 1412, 1413, 1414 open no lockouts DG output breaker CS in A/T (Unless surv test sw in TEST)
What interlocks must be satisfied to close a unit x-tie breaker?
Breaker 1414
What interlocks must be satisfied to manually close UAT feed? Breaker 1431
What interlocks must be met to Auto close UAT feed?
Breaker 1431
What interlocks must be met to manually close SAT feed? Breaker 1432
ESF to non esf bus x-tie open 1411
Sync scope on
What interlocks must be met to auto close SAT feed?
1432
What is RAST? Time delay?
R=Reclose
A=Alive bus
S=Sync check
T=Timed (set @1sec)
Breaker will reclose after 1 sec if bus is alive and in sync
What bus powers the rod drive MGs?
133Y and 134Y
What busses power the jockey pumps?
Jockey A 134 U
Jockey B 133 U
What busses power the RCFC?
131X RCFC 1A and 1C
132X RCFC 1B and 1D
Main power transformer (MPT) ratings
60% capacity each
23.7 to 345KV step up
Forced oil and air cooling (FOA/FOA)
Fans and oil pumps auto start when Q10/Q20 bkr closed
MPT trips
Differential overcurrent*
Overexcitation
Ground overcurrent
Sudden pressure *
Any MPT trip will actuate 86G1A and 86G1B which trips main generator