SI signals
CVI signals
Manual phase A
Manual CS/phase B
SI
Cnmt area high rad AR11/12J
FWI signals
SI
P14
P4 with low Tave 564F
Steamline isolation signals
Manual, 1/2 switches
Steamline low pressure, 640 psig, 2/3 on 1/4 SGs
Steamline high neg rate, >100 psig drop w/in 50 sec 2/3 1/4 SG
Cnmt hi-2 pressure, 8.2 psig, 2/3
CS/Phase B signals
Manual 2/2 switches
Cnmt hi pressure, 20 psig 2/4
CS/Phase B can/can not be reset with initiating signal still present
CAN
Which actuations can be reset with initiating signal still present?
Containment Phase A
Containment Phase B
CVI
Control room vent actuation (from SI)
CS actuation
P-4 with low Tave FW isolation
How to reset a FWI after a SI signal
How to reset a FWI after a P-14
Once SI has been blocked, how can the block be removed?
Cycle reactor trip breakers to toggle P-4. This will unblock the SI
If a reactor trip breaker doesn’t open with a SI, __________ until _______.
SI cannot be reset on that train until that RTB is opened
Train A SSPS will de-energize ______ UV coils to open the breakers. Train B SSPS will de-energize _____ UV coils.
Train A, RTA and BYB UV coils
Train B, RTB and BYA UV coils
Reactor trip bypass breaker trips
Reactor trip breaker trips
Reactor trip bypass breaker trips when in test
Bypass breaker CS to trip
UV coil de-energized
Bypass breaker indication lights on PM05J lit only when _____.
Bypass breaker racked in with fuses installed.
SI recirc sump isol valve reset PB will _____ and if not reset will ______.
Remove the auto open signal to SI 8811a/b and remove an auto signal to CV8110/8111
Prevent closure of ACB 1411
AUTO SI BLOCKED light will be ______ if _______.
Fast flashing if one train wasnt blocked because of RT or bypass breaker not open
SI can be reset After a ______ second time delay,
60 second