Purpose of CW
Circ water pump trips
Manual Phase OC Ground OC Loss of exciter field 4kv bus UV
CW pump classification
6000 HP
214500 GPM
CW pump interlocks (to start)
When does discharge valve start to open after pump start?
Avoid throttling discharge valve to ______ to ensure min flow through the pump.
<40%
Discharge valve _____ on pump trip. CW breaker position input to _____.
Closes
C-9
Close discharge to ______ prior to tripping CW pump to ______.
25%
Prevent excessive backflow
Power supplies of the CW pumps is 1A____1B_____1C_____.
A and C 143
B 144
_____normally supplies the CW pps oil cooler and seal water.
_____ discharge header provides a backup supply
WS
CW
Natural draft cooling tower turbine trip interlock:
The NDCT turbine trip interlock is normally ______ to prevent______.
Bypassed to prevent stirring up debris and clogging cold water basin screens.
To reopen the riser valves, must have _____ and _____.
Turbine trip signal removed
Turbine throttle valves reopened
CW low discharge pressure will alarm at _____.
35#
C-9 (condenser permissive) to be made up must have _____ and any _______.
<7.0 in HgA -and- any 1 of 3 CW pump breaker closed
The function of C-9 is to ______ and can/can not be bypassed.
Block normal steam dump ops
Can not
Sodium hypochlorite can only be in service for _______ hours, per _____ per _____.
2 hours per unit per day
Sodium bisulfate must be added any time sodium hypochlorite in service or ______violation will occur.
NPDES
Blowdown flow must be maintained ______ gpm for dilution when _______.
> 10,000
releasing a radwaste release tank to the river
Traveling screens are on an automatic timer to run for ______ for 0A and _____ for 0B once every _____.
25 minutes
55 minutes
12 hours
Traveling screens also operate on high DP of ______ in slow and shifts to _______ at _______.
6” H20
Fast
12” H20
CW makeup pump trips 6
-Phase or ground OC
-Bus UV
-Manual
-Emergency trip PBs (MCR or local)
-15 seconds after pump start if
a. Discharge valve has not come off of closed seat
b. Discharge valve closes
0B pump only: trips on both sliding gates closed
0CW220 is the _______ and maintains flume and intake bay level at setpoint from controller in ______.
Makeup valve
MCR
If you emergency trip any one ______, you should trip all running______ to help prevent _______ damage.
CW MU pump
CW MU pump
Backflow